FDMR
Fire Damper (FD/MFD) EIS Classified
FDMR - The FDMR is a circular fire damper available in both manual (FD) and motorised (MFD) formats classified for Integrity (E), Insulation (I), and Smoke leakage (S) used to maintain fire performance of fire separating elements where penetrated by air handling ducts.
Properties
•Dampers from ø 100 to ø 800 mm
•CE and UKCA Certified acc. to BS EN 15650
•Tested in accordance with BS EN 1366-2
•Classified acc. to BS EN 13501-3+A1
•Fire resistance up to EI 120 S - 500 Pa
•External Casing leakage class ATC 3 Internal leakage class 3 acc. to BS EN 1751
•Corrosion resistant acc. to BS EN 15650
•Cycling class C10000 acc. to BS EN 15650
•Available as manual FD or as 230v/24v MFD
•Maximum air speed through opened damper of 12 m/s and pressure difference 1200 Pa
Specifications
The FDMR fire damper is available in both manual (FD) and motorised (MFD) versions. The manual FD can be operated and functionally tested with an externally resettable manual handle which is locked in the open position and held in place with a fusible link. On thermal activation of the link (at 72°C unless otherwise specified) the damper fails to the closed position. For the MFD, the actuator drives the damper open when powered and tensions an internal spring, the damper will spring close on activation of a thermal fuse (BAT), interruption of the power supply, or activation from a fire damper control system. The FDMR damper includes an access hatch built into the casing along with an endoscopic camera slot for inspection/maintenance. The FDMR damper can also be provided with factory fitted fixing brackets to assist with the installation of the damper.